Read-only technician viewF1 live sample
Outside Air74°F
Product / site statusProtectedBoth probes inside range
Time-to-Limit46.4mDoor exposure watch
Suction pressure
42PSI
Ideal range 0-80psi

Calculated saturated
Suction Temp -37.6°F

Discharge pressure
238PSI
Ideal range 120-320psi

Calculated saturated
Discharge Temp -35.4°F

Sensor snapshot14 layout points • tap dots to graph
Product Probe Temp 1-37.1°CGraph
Product Probe Temp 2-37.1°CGraph
Suction Temp-37.6°FGauge context
Superheat3.6°FGauge context
Defrost Term Temp-39.1°FGauge context
Discharge Temp-35.4°FGauge context
Return Air Temp-33.9°FGauge context
Evap Temp TD1.6°FGauge context
Door Open Time46.4 minsGauge context
Door Open Count17Gauge context
Vibration.543 IMPGauge context
Hot Gas Temp178°FGauge context
Sub cooling27°FGauge context
COMPRESSOR AMPS32.5 AGauge context
OutputsStatus
Liquid Line ValveOnOpen
Evap FansOnRunning
Defrost HeatersOffOff
DoorClosed
15 mins
Y: Selected trace min/maxX: 15 mins window
29.3-37.9015 minsFreezer 1 live trace • selected pointsProduct Probe Temp 1 / Suction Temp / Discharge Temp / COMPRESSOR AMPS
Last events
300s event replayRepeated start window with elevated amps and stable product probes.-36.8-37.5-300sAlarmAlarm: Product Probe Temp 1 -37.35 °C
Suggested pathVerify compressor amps, contactor/capacitor behavior, suction pressure recovery, and door exposure before dispatch.
Refrigeration chatbot
Freezer 1 is protected. Active event 422: Compressor short cycle. Repeated start window with elevated amps and stable product probes.

Demo Cryo Company • technician workbench

Gauges, traces, and repair context before the truck rolls.

This fictional demo view gives field teams pressure, amperage, vibration, superheat, product condition, controller evidence, event replay, suggested checks, and repair verification.

Computer technician layout

Same original 14 points, rebuilt for desktop width.

The computer page keeps Mike’s point order intact across Freezer 1, Freezer 2, and ANTE RM, but uses the wider screen for side-by-side comparison instead of stacking everything like the phone.

Protected / service watch

Freezer 1

Original layout points, ordered for wide technician review.

F1
01Product Probe Temp 1-37.1°C
02Product Probe Temp 2-37.1°C
03Suction Temp-37.6°F
04Superheat3.6°F
05Defrost Term Temp-39.1°F
06Discharge Temp-35.4°F
07Return Air Temp-33.9°F
08Evap Temp TD1.6°F
09Door Open Time46.4 mins
10Door Open Count17
11Vibration.543 IMP
12Hot Gas Temp178°F
13Sub cooling27°F
14COMPRESSOR AMPS32.5 A
Output / Status — separate from the 14 data pointsLiquid Line ValveEvap FansDefrost HeatersDoor
Protected / runtime watch

Freezer 2

Same 14-point order so technicians do not relearn the page per asset.

F2
01Product Probe Temp 1-36.9°C
02Product Probe Temp 2-36.9°C
03Suction Temp-37.6°F
04Superheat3.6°F
05Defrost Term Temp-39.1°F
06Discharge Temp-35.4°F
07Return Air Temp-33.9°F
08Evap Temp TD1.6°F
09Door Open Time22.7 mins
10Door Open Count11
11Vibration.388 IMP
12Hot Gas Temp178°F
13Sub cooling27°F
14COMPRESSOR AMPS27.4 A
Output / Status — separate from the 14 data pointsLiquid Line ValveEvap FansDefrost HeatersDoor
Normal / door discipline

ANTE RM

Same layout positions; freezer-only refrigeration points stay visible as N/A.

AR
01Product Probe Temp 1N/A
02Product Probe Temp 2N/A
03Suction TempN/A
04SuperheatN/A
05Defrost Term TempN/A
06Discharge TempN/A
07Return Air Temp36.1°F
08Evap Temp TDN/A
09Door Open Time46.4 mins
10Door Open Count36
11VibrationN/A
12Hot Gas TempN/A
13Sub coolingN/A
14COMPRESSOR AMPS0 A
Output / Status — separate from the 14 data pointsLiquid Line ValveEvap FansDefrost HeatersDoor

Service gauges

The first read looks like field instrumentation, not a spreadsheet.

Each gauge ties to a selected site, asset, and live point so the technician can focus on what changed.

42PSI

Suction

stable

0 to 80 PSI
238PSI

Discharge

watch head pressure

120 to 320 PSI
18.6A

Compressor

+22% vs baseline

0 to 28 A
0.42ips

Vibration

bearing band elevated

0 to 0.7 ips
9.8F

Superheat

inside target

0 to 24 F
-35.4C

Product

protected

-45 to -10 C

Digital Mechanic

300-second incident replay

Controller-style traces line up the pre-alarm window so the technician can see what changed before the call.

-300sAlarm
Product probe-35.4 Cinside protected range
Compressor amps+22%startup band above baseline
Suction pressure42 PSIstable with recovery under watch
Vibration RMS0.42 ipsbearing band elevated
Door / fan / LLVnormalno behavioral trigger found

Trace watchlist

Controller graph controls

Selected asset, selected trace, alarm overlay, differential view, and service-record export.

Product Probe Temp 1Available tracewatch
Product Probe Temp 2Available tracewatch
Suction TempAvailable tracewatch
SuperheatAvailable tracewatch
Defrost Term TempAvailable tracewatch
Discharge TempAvailable tracewatch
Return Air TempAvailable tracewatch
Evap Temp TDAvailable tracewatch
Door Open TimeAvailable tracewatch
Door Open CountAvailable tracewatch
VibrationAvailable tracewatch
Hot Gas TempAvailable tracewatch
Sub coolingAvailable tracewatch
COMPRESSOR AMPSAvailable tracewatch
Digital Mechanic

Thermodynamic calculations

Suction/discharge pressure, saturation conversion, superheat, subcooling, pulldown velocity, thermal decay rate, and defrost termination delta.

Digital Mechanic

Electrical + vibration signature

Startup amperage, running amperage, voltage sag, vibration RMS/peak, and bearing/rotor indicators for the Mechanical Heartbeat.

Digital Mechanic

Controller-style graph

Date range, device selector, trace selector, alarm overlay, absolute/differential view, and export to service records.

Digital Mechanic

One-trip service workflow

Likely cause, confidence score, suggested part, check-step guide, repair-order handoff, Verify Repair, and Baseline Reset after confirmed operation.

Repair-order support

F1 compressor short-cycle investigation

Startup amps are 22% above baseline with elevated vibration band and delayed post-defrost recovery. Check capacitor, contactor, fan state, pressure behavior, and refrigerant charge indicators before replacing compressor.

Guardrail

AI gives evidence. The technician owns the fix.

The platform supports licensed mechanical judgment without replacing field authority.